60*
Master 601
Slave1 602
Slave2 603
Slave3 604
Comp PCB EEP-
ROM error
Error No.
Error Type
Error Point
Main Reasons
EEPROM Access error
and Check SUM error
1. EEPROM contact defect/wrong insertion
2. Different EEPROM Version
3. ODU Comp PCB assembly damage
n
Error Diagnosis and Countermeasure Flow Chart
Is EEPROM insertion normal?
No
Yes
Recheck power and installation condition
1.Check EEPROM insert direction/connection condition
2.Check EEPROM Check SUM
’
Replace if abnormality found
Is Comp PCB assembly normal?
No
Yes
Replace Comp PCB assembly
* Inverter EEPROM inserting point
* Right inserting direction of inverter EEPROM
❊
Note : Replace after power off
Check IC02L
Summary of Contents for ARNU05GL1G2