Function
FDD Check list
* Please check the following.
1. Automatic address setting has been preceded by a test drive will proceed on the premise.
After installation, auto address must be checked because it is related the number of installation
2. 3 minutes after the initial power on test drive at one point.
Aafter the power on, MICOM data reset and communication with indoor unit time is 3minute
3. Indoor unit must be 7 series over
4. In FDD test drive, state of the test drive and error are displayed using 7 segment.
The process of the test drive and state of error are displayed using only the master outdoor uint.
5. If the error is occurred during the test drive, it will be operated the last step after turn off the test drive.
Ater the dip switch off, pressing the black button for 2 seconds in order to reset all data and return to operation
standby state
6. SW04C (X: Cancel) button and SW01C (
●
: execute) button is pressed for more than 5 seconds at the same
time when the test drive must be turned of the reason of abrupt trouble during test drive.
7. All indoor units are turned off or the results are displayed after 90 seconds when the test drive is over.
8. First, please pressing the main PCB reset button for 3 minutes when you want to use all FDD functions.
9. Normal test run is operated when you use more than LGMV 7.0.3 version.