Troubleshooting Guide
- 131 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Power cable or communication
cable is not connected
2. Defect of outdoor Cycle/External
PCB
Error No.
Error Type
Error Point
Main Reasons
Cycle controller of Master unit of
Master unit canʼt receive signal
from External controller
Communication Error
between
(Main PCB
’
External
PCB)
145*
Master
1451
Slave1
1452
Slave2
1453
Slave3
1454
Is communication LED
(Yellow) of
External PCB on?
Is communication cable
connected correctly?
Re-connect Power cable
Re-connect communication cable
Replace External PCB
External Communication Connector
External Communication LED
Yes
Yes
No
Is Main PCB normal
Replace Main PCB
Yes
No
No
Communication Connector &
LED in Main PCB
Communication Connector &
LED in External PCB
* The Method of checking Main PCB and External PCB (If normal, communication LED blinks)
n
Error diagnosis and countermeasure flow chart
Summary of Contents for ARNU05GL1G2