Table 54:
BACnet and MODBUS Points List, continued.
Variable
Description
Active
Text
Inactive
Text
BACnet
MODBUS
Object
Instance
Object
Type
Access
Hyst Index Register
Type Size
Analog Values – Read Only, continued.
Electric_Heater_1_Analog_
Output
Electric Heater 1 Analog
Output
221
AV
ReadCOV_
NoWrite 0.1 30514 Input
2
Energy_Recovery_Analog_
Output
Energy Recovery Analog
Output
229
AV
ReadCOV_
NoWrite 0.1 30518 Input
2
Exhaust_Fan_Speed_
Analog_Output
Exhaust Fan Speed
Analog Output
231
AV
ReadCOV_
NoWrite 0.1 30522 Input
2
Hot_Gas_Reheat_Analog_
Output
Hot Gas Reheat Analog
Output
235
AV
ReadCOV_
NoWrite 0.1 30524 Input
2
Hot_Water_Valve_1_Analog_
Output
Hot Water Valve 1
Analog Output
236
AV
ReadCOV_
NoWrite 0.1 30526 Input
2
Mod_Gas_Furnace_1_
Analog_Output
Mod Gas Furnace 1
Analog Output
242
AV
ReadCOV_
NoWrite 0.1 30538 Input
2
Outside_Air_Damper_
Analog_Output
Outside Air Damper
Analog Output
250
AV
ReadCOV_
NoWrite 0.1 30542 Input
2
Supply_Fan_Speed_Analog_
Output
Supply Fan Speed
Analog Output
264
AV
ReadCOV_
NoWrite 0.1 30558 Input
2
Modulating_Compressor_
Analog_Output_ BMS
Modulating Compressor
Analog Output - BMS
285
AV
ReadCOV_
NoWrite 0.1 30586 Input
2
Circuit_A_Sat_Discharge_
Temperature
Circuit A Saturated
Discharge Temperature
286
AV
ReadCOV_
NoWrite 0.1 30588 Input
2
Circuit_B_Sat_Discharge_
Temperature
Circuit B Saturated
Discharge Temperature
287
AV
ReadCOV_
NoWrite 0.1 30590 Input
2
Binary Inputs – Read Only
Comp_Circ_A_High_
Pressure_Digital_ Input
Circuit A High Pressure
Switch
Alarm
Normal
3
BI
ReadCOV_
NoWrite
0 10052 Discrete
Comp_Circ_A_Low_
Pressure_Digital_Input
Circuit A Low Pressure
Switch
Alarm
Normal
4
BI
ReadCOV_
NoWrite
0 10053 Discrete
Comp_Circ_B_High_
Pressure_Digital_ Input
Circuit B High Pressure
Switch
Alarm
Normal
5
BI
ReadCOV_
NoWrite
0 10054 Discrete
Comp_Circ_B_Low_
Pressure_Digital_Input
Circuit B Low Pressure
Switch
Alarm
Normal
6
BI
ReadCOV_
NoWrite
0 10055 Discrete
Controls_Lite_
Dehumidification_
Request_ Digital_Input
Controls Lite
Dehumidification
Request Status
Dehumidify
Cool
19
BI
ReadCOV_
NoWrite
0 10068 Discrete
Controls_Lite_Cool_Heat_
Request_ Digital_Input
Controls Lite Cool Heat
Request Status
Heating
Cooling
20
BI
ReadCOV_
NoWrite
0 10069 Discrete
Drain_Pan_Alarm_Digital_
Input
Drain Pan Alarm Digital
Input Status
Alarm
Normal
21
BI
ReadCOV_
NoWrite
0 10070 Discrete
EAD_End_Switch_Digital_
Input
Exhaust Air Damper End
Switch Digital Input
Status
Closed
Open
22
BI
ReadCOV_
NoWrite
0 10071 Discrete
Exhaust_Fan_1_Status_
Digital_Input
Exhaust Fan 1 Status
On
Off
23
BI
ReadCOV_
NoWrite
0 10072 Discrete
Freeze_Stat_Alarm_Digital_
Input
Freeze Stat Alarm
Digital Input Status
Alarm
Normal
28
BI
ReadCOV_
NoWrite
0 10077 Discrete
OAD_End_Switch_Digital_
Input
OAD End Switch Digital
Input Status
Closed
Open
52
BI
ReadCOV_
NoWrite
0 10101 Discrete
Occupancy_Digital_Input
Occupancy Digital Input
Status
Occupied Unoccupied
53
BI
ReadCOV_
NoWrite
0 10102 Discrete
CONTROLLER
BACnet and MODBUS Points