104
Rooftop Dedicated Outdoor
Air System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 63: LonTalk Points List.
Access
NV Name
SNVT Type
Description
Notes
Read-Only Points
nvo
LatestAlm
count (8)
Most recent alarm
See Alarms Data Table
nvo
UnitStatus
count (8)
Startup and Operation Information
See Unit Status Mode Table
nvo
ExhCFM
flow_p (161)
Total Exhaust Fan CFM
Multiply by 100 for CFM.
nvo
OACFM
flow_p (161)
OAD CFM
Multiply by 100 for CFM.
nvo
SupCFM
flow_p (161)
Total Supply Fan CFM
Multiply by 100 for CFM.
nvo
CoolingRamp1
lev_percent (81)
Cooling Ramp 1 Status Value
Compressor Capacity
nvo
CWV1Out
lev_percent (81)
Chilled Water 1 Valve Analog Output
nvo
ElecHeat1Out
lev_percent (81)
Electric Heater 1 Analog Output
nvo
ERecoveryOut
lev_percent (81)
Energy Recovery Analog Output
nvo
ExhFan1Out
lev_percent (81)
Exhaust Fan Speed Analog Output
nvo
HeatingRamp
lev_percent (81)
Heating Ramp
nvo
HGROut
lev_percent (81)
Hot Gas Reheat Analog Output
nvo
HPumpHeatRamp
lev_percent (81)
Heat Pump Heating Ramp
Compressor Capacity
nvo
HWV1Out
lev_percent (81)
Hot Water Valve 1 Analog Output
nvo
ModCompOutBMS
lev_percent (81)
Modulating Compressor Analog Output BMS
nvo
ModFurn1Out
lev_percent (81)
Mod Gas Furnace 1 Analog Output
nvo
OADOutput
lev_percent (81)
Outside Air Damper Analog Output
nvo
OutsideRH
lev_percent (81)
Outside % Relative Humidity
nvo
SpaceRH
lev_percent (81)
Space % Relative Humidity
nvo
SupFan1Out
lev_percent (81)
Supply Fan Speed Analog Output
nvo
Space1CO2
ppm (29)
Space 1 CO
2
ppm
nvo
SpacePress
press_p (113)
Space Static Pressure
nvo
SupDuctPress
press_p (113)
Supply Duct Static Pressure
nvo
DigAlarms
state (83)
Digital Alarm States
16 bit packed
nvo
DigAlarms.bit00
state.bit00
Circuit A High Pressure Switch
0=Normal 1=Alarm
nvo
DigAlarms.bit01
state.bit01
Circuit A Low Pressure Switch
0=Normal 1=Alarm
nvo
DigAlarms.bit02
state.bit02
Circuit B High Pressure Switch
0=Normal 1=Alarm
nvo
DigAlarms.bit03
state.bit03
Circuit B Low Pressure Switch
0=Normal 1=Alarm
nvo
DigAlarms.bit04
state.bit04
Drain Pan Alarm
0=Normal 1=Alarm
nvo
DigAlarms.bit05
state.bit05
Freeze Stat Alarm
0=Normal 1=Alarm
nvo
DigAlarms.bit06
state.bit06
Outside Filter Alarm (Dirty Filter)
0=Normal 1=Alarm
nvo
DigAlarms.bit07
state.bit07
Shutdown alarm status
0=Normal 1=Alarm
nvo
DigStatus
state (83)
Digital Status States
16 bit packed
nvo
DigStatus.bit00
state.bit00
Compressor 1 Enable Digital Output
0=Off 1=On
nvo
DigStatus.bit01
state.bit01
Compressor 2 Enable Digital Output
0=Off 1=On
nvo
DigStatus.bit02
state.bit02
Compressor 3 Enable Digital Output
0=Off 1=On
nvo
DigStatus.bit03
state.bit03
Compressor 4 Enable Digital Output
0=Off 1=On
nvo
DigStatus.bit04
state.bit04
Condenser Fan 1 Digital Output
0=Off 1=On
nvo
DigStatus.bit05
state.bit05
Condenser Fan 2 Digital Output
0=Off 1=On
nvo
DigStatus.bit06
state.bit06
Condenser Fan 3 Digital Output
0=Off 1=On
nvo
DigStatus.bit07
state.bit07
Furnace 1 Stage 1 Digital Output
0=Off 1=On
nvo
DigStatus.bit08
state.bit08
Furnace 2 Stage 1 Digital Output
0=Off 1=On
CONTROLLER