Table 58:
BACnet and MODBUS Points List, continued.
Variable
Description
Active
Text
Inactive
Text
BACnet
MODBUS
Object
Instance
Object
Type
Access
Hyst Index Register
Type Size
Binary Values – Read Only, continued.
Comp_Circ_A_High_Pressure_
Alarm.Active
Comp Circ A High
Pressure Alarm
Alarm
Normal
395
BV
ReadCOV_NoWrite 0 10346 Discrete
Comp_Circ_A_Low_Pressure_
Alarm.Active
Comp Circ A Low
Pressure Alarm
Alarm
Normal
396
BV
ReadCOV_NoWrite 0 10347 Discrete
Comp_Circ_B_High_Pressure_
Alarm.Active
Comp Circ B High
Pressure Alarm
Alarm
Normal
397
BV
ReadCOV_NoWrite 0 10348 Discrete
Comp_Circ_B_Low_Pressure_
Alarm.Active
Comp Circ B Low
Pressure Alarm
Alarm
Normal
398
BV
ReadCOV_NoWrite 0 10349 Discrete
Comp_Maintenance_Alarm.
Active
Comp
Maintenance
Alarm
Alarm
Normal
411
BV
ReadCOV_NoWrite 0 10362 Discrete
Damper_End_Switch_Alarm.
Active
Damper End
Switch Alarm
Alarm
Normal
420
BV
ReadCOV_NoWrite 0 10371 Discrete
Drain_Pan_Alarm.Active
Drain Pan Alarm
Alarm
Normal
422
BV
ReadCOV_NoWrite 0 10372 Discrete
Exhaust_Fan_1_Alarm.Active
Exhaust Fan 1
Alarm
Alarm
Normal
423
BV
ReadCOV_NoWrite 0 10373 Discrete
Exhaust_Fan_1_CFM_Analog_
Input_Alarm. Active
Exhaust Fan 1
CFM Analog Input
Alarm
Alarm
Normal
424
BV
ReadCOV_NoWrite 0 10374 Discrete
Exhaust_Temperature_Sensor_
Alarm.Active
Exhaust
Temperature
Sensor Alarm
Alarm
Normal
433
BV
ReadCOV_NoWrite 0 10383 Discrete
Expansion_Board_1_Alarm.
Active
Expansion Board 1
Alarm
Alarm
Normal
434
BV
ReadCOV_NoWrite 0 10384 Discrete
Expansion_Board_2_Alarm.
Active
Expansion Board 2
Alarm
Alarm
Normal
435
BV
ReadCOV_NoWrite 0 10385 Discrete
Expansion_Board_3_Alarm.
Active
Expansion Board 3
Alarm
Alarm
Normal
436
BV
ReadCOV_NoWrite 0 10386 Discrete
Freeze_Stat_Alarm.Active
Freeze Stat Alarm Alarm
Normal
441
BV
ReadCOV_NoWrite 0 10391 Discrete
Internal_Board_Temp_Alarm.
Active
Internal Board
Temp Alarm
Alarm
Normal
498
BV
ReadCOV_NoWrite 0 10448 Discrete
Mixed_Temperature_Sensor_
Alarm.Active
Mixed Temperature
Sensor Alarm
Alarm
Normal
502
BV
ReadCOV_NoWrite 0 10452 Discrete
Multi_Channel_Conf_Alarm.
Active
Multi Channel Conf
Alarm
Alarm
Normal
503
BV
ReadCOV_NoWrite 0 10453 Discrete
OAD_CFM_Analog_Input_
Alarm.Active
OAD CFM Analog
Input Alarm
Alarm
Normal
506
BV
ReadCOV_NoWrite 0 10456 Discrete
Outside_Air_Temperature_
Sensor_Alarm. Active
Outside Air
Temperature
Sensor Alarm
Alarm
Normal
507
BV
ReadCOV_NoWrite 0 10457 Discrete
Outside_Filter_Alarm.Active
Outside Filter
Alarm
Alarm
Normal
508
BV
ReadCOV_NoWrite 0 10458 Discrete
Outside_RH_Sensor_Alarm.
Active
Outside RH
Sensor Alarm
Alarm
Normal
509
BV
ReadCOV_NoWrite 0 10459 Discrete
Return_RH_Sensor_Alarm.
Active
Return RH Sensor
Alarm
Alarm
Normal
532
BV
ReadCOV_NoWrite 0 10482 Discrete
Return_Temperature_Sensor_
Alarm.Active
Return
Temperature
Sensor Alarm
Alarm
Normal
533
BV
ReadCOV_NoWrite 0 10483 Discrete
CONTROLLER
BACnet and MODBUS Points