54
Rooftop Dedicated Outdoor
Air System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 26: c.pCOe Expansion Board 2 Analog Inputs / Outputs and Digital Outputs.
Analog Inputs
Drawing Reference
Terminal
Label
Unit Connection
Sensor Type
Range
1
J2
U1
Analog output
1
J2
U2
Space CO2 level
0–10 Vdc
0–2000 ppm
1
J2
U3
Outside air flow measuring station
0–10 Vdc
0–1"wc or 0–0.5"wc
1
J2
U4
Supply fan air flow measuring station
0–10 Vdc
0–30" wc
1
J2
U5
Exhaust fan air flow measuring station
0–10 Vdc
0–30" wc
1
J2
U6
OA/RA damper control, BMS input b
0–10 Vdc
0–100%
1
J2
U7
Supply fan control, BMS input c
0–10 Vdc
0–100%
1
J2
U8
Exhaust fan control, BMS input c
0–10 Vdc
0–100%
1
J2
U9
Unassigned
1
J2
U10
Used as digital input.
Analog Outputs
Drawing Reference
Terminal
Label
Unit Connection
Sensor Type
Range
1
J2
U1
Electric heat capacity output d
0–10 Vdc
0–100%
Digital Outputs
Drawing Reference
Terminal
Label
Unit Connection
Position Indicates
2
J10
NO1
Unassigned
2
J10
NO2
Unassigned
2
J11
NO3
Unassigned
2
J11
NO4
Unassigned
2
J11
NO5
Unassigned
2
J12
NO6
Unassigned
2
J12
NC6
Unassigned
CONTROLLER
Overview
Overview