Rooftop Dedicated Outdoor
Air System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 24:
Main Board Analog and Digital Outputs.
Analog Outputs
Drawing Reference Terminal
Label
Unit Connection
Sensor Type
Range
7
J4
Y1
Modulating compressor output or cooling
capacity output
a
Use-dependent
0–100%
7
J4
Y2
Condenser fan VFD output Circ. A; or water
valve output Circ. A
b
0–10 Vdc
0–100%
7
J4
Y3
Hot gas reheat valve output
0–10 Vdc
0–100%
7
J4
Y4
Condenser fan VFD output Circ. B
c
or water
valve output Circ. B
d
0–10 Vdc
0–100%
3
J6
U7
OA/RA damper output
0–10 Vdc
0–100%
3
J6
U8
Supply fan speed output
0–10 Vdc
0–100%
Digital Outputs
Drawing Reference Terminal
Label
Unit Connection
Position Indicates
15
J12
NO1
Compressor 1 start
Closed = start compressor
15
J12
NO2
Compressor 2 start
Closed = start compressor
15
J12
NO3
Compressor 3 start
Closed = start compressor
15
J13
NO4
Compressor 4 start
Closed = start compressor
15
J13
NO5
Supply fan start
Closed = start fan
15
J13
NO6
Exhaust fan start
Closed = start fan
15
J14
NO7
Actuator power
Closed = enabled
15
J15
NO8
Global alarm output, BMS output
Closed = enabled
15
J15
NO8
Unassigned
15
J16
NO9
Condenser fan VFD start
Closed = start condenser fan
15
J16
NO10
Condenser fan stage 2 start
Closed = start condenser fan
15
J16
NO11
Condenser fan stage 3 start
Closed = start condenser fan
15
J17
NO12
Unassigned
15
J17
NC12
Inverter scroll compressor E-stop
e
Open = stop compressor
15
J18
NO13
Reversing valve output
f
Closed = heating
15
J18
NC13
Unassigned
a
Chilled water option, no compressors (0 to 10 VDC, direct or reverse).
b
Water source heat pump units only.
c
352 Casing with Active Head Pressure control 2.0.
d
Water source heat pump units with more than one compressor.
d
Units with inverter scroll compressor.
f
Heat pump units.
CONTROLLER
Overview