78
Rooftop Dedicated Outdoor
Air System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 36: Energy Recovery Set-Points Data Table.
Control Variable
Default
Min.
Max.
Notes
Defrost Ramp Exhaust Set-point
36.0°F
15.0°F
50.0°F
Heat Wheel
Minimum Speed
20%
0%
100%
Enable Jog
Enabled (X)
Disabled (□)
Enabled (X)
Jog Enable Delay
60 min.
10 min.
300 min.
Jog Duration
2 min.
1 min.
99 min.
Set-point availability varies based on unit configuration.
Table 37: Fan Control Set-Points Data Table.
Control Variable
Default
Min.
Max.
Notes
Supply Fan Control
Enable Delay
5 sec.
0 sec.
60 sec.
Minimum Speed
50%
50%
100%
Maximum Speed
100%
50%
100%
Constant Volume Set-point
Occupied
100%
50%
100%
Unoccupied
60%
50%
100%
Duct Static Set-point
1.00
"
wc
0.00
"
wc
5.00
"
wc
Space Static Set-point
0.05
"
wc
-0.50
"
wc
0.50
"
wc
Airflow Set-point
0 CFM
0 CFM
999999 CFM
Soft Shutdown Enable
Set-point
85.0°F
70.0°F
150.0°F
Delay
120 sec.
0 sec.
999 sec.
Exhaust Fan Control
Constant Volume Set-point Enable Delay
0 sec.
0 sec.
60 sec.
Constant Volume Set-point Enable When OAD
>=
15%
0%
99%
Minimum Speed
25%
25%
100%
Maximum Speed
100%
25%
100%
Constant Volume Set-point Occupied
100%
25%
100%
Constant Volume Set-point Unoccupied
60%
25%
100%
Space Static Set-point
0.05
"
wc
-0.50
"
wc
0.50
"
wc
Supply Tracking Offset
-10%
-100%
100%
Airflow Set-point
0 CFM
0 CFM
999999 cfmCFM
CONTROLLER
Set-Points Data Tables