Table 22: CAREL c.cPO Control Board Terminal Connections.
Table 23:
Main Board Analog and Digital Inputs.
Drawing Reference
Description
Drawing Reference
Description
1
Power connection [G(+), G0(-)]
12
Reserved
2
+Vterm: power supply for additional terminal
+5 VREF: power supply for ratiometric probes
13
Ethernet port 1
3
Universal inputs/outputs
14
Ethernet port 2
4
+Vdc: power supply for active probes
15
Relay digital outputs
5
Button for setting pLAN address, second display, LED
16
BMS2 port
6
VG: power supply at voltage A a for opto-isolated analog
output VG0: power to optically-isolated analog output, 0
Vac/Vdc
17
Fieldbus2 port
7
Analog outputs
18
Jumpers for selecting fieldbus/BMS
8
ID: digital inputs for voltage A (24 VAC or 28-36 VDC)
25
USB Host Port (Master)
9
ID: digital inputs for voltage A (24 VAC or 28-36 VDC)
IDH: digital inputs for voltage B (230V 50/60Hz)
26
USB Host Port (Slave)
10
pLAN telephone connector for handheld display
27
Faston (blade) for ground to
Ethernet port
11
pLAN connection. Do not use.
28
Built-in and Keypad
Analog Inputs
Drawing Reference Terminal
Label
Unit Connection
Sensor Type
Range
3
J2
U1
Refrigerant pressure transducer, Circuit A
0.5–4.5 V
a
0–650 psig
3
J2
U2
Refrigerant pressure transducer, Circuit B
0.5–4.5 V
a
0–650 psig
3
J2
U3
Supply air temperature
CAREL NTC 10K Type 4
3
J3
U4
Cooling coil leaving air temperature
CAREL NTC 10K Type 4
3
J3
U5
Outside air temperature
CAREL NTC 10K Type 4
3
J6
U6
Outside air humidity
0–10 Vdc
0–100%
3
J6
U7
Used as analog output.
3
J6
U8
Used as analog output.
Digital Inputs
Drawing Reference Terminal
Label
Unit Connection
Position Indicates
8
J5
ID1
Supply air temperature
Closed = fan on
8
J5
ID2
High pressure switch, Circuit A
Closed = normal
8
J5
ID3
Low pressure switch, Circuit A
Closed = normal
8
J5
ID4
Occupancy input, BMS input
Closed = occupied
8
J5
ID5
OA/RA damper end switch
Closed = end switch made and damper(s) open
8
J5
ID6
Shutdown input, BMS input
Closed = run
8
J5
ID7
High pressure switch, Circuit B
Closed = normal
8
J5
ID8
Low pressure switch, Circuit B
Closed = normal
8
J7
ID9
Exhaust fan status
Closed = fan on
8
J7
ID10
Filter pressure switch
Closed = dirty filter alarm
8
J7
ID11
Energy recovery wheel status
Closed = stopped alarm
8
J7
ID12
Low temp protection input, freeze stat
b
Closed = normal
9
J8
ID13H
Unassigned
9
J8
ID13
Condensate drain pan switch
Closed = alarm
9
J8
ID14
Remote start input, BMS input
Closed = run
9
J8
ID14H
Unassigned
a
Radiometric transducers.
b
Chilled water or hot water units only.