88
Rooftop Dedicated Outdoor
Air System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 47: Alarm Data, continued.
Alarm ID
Alarm Screen Line 1
Alarm Screen Line 2
Reset Type
Lockout
Action Type
Notes
80
Supply Water Temp 1
Sensor Value Not Valid
Auto
Disable Compressors
WSHP
81
Return Water Temp 1
Sensor Value Not Valid
Auto
Disable Compressors
WSHP
82
Reac Whl In Temp
Sensor Value Not Valid
Auto
50% DFF Control
83
Reac Whl Out Temp
Sensor Value Not Valid
Auto
Informational
84 - 85
Cold Coil (x) Temp
Sensor Value Not Valid
Auto
Disable Cooling Ramp
86 - 87
Cold Coil (x) RH
Sensor Value Not Valid
Auto
Informational
88
Return Filter Pressure
Sensor Value Not Valid
Auto
Informational
89
Space 1 CO2
Sensor Value Not Valid
Auto
Disable CO
2
90
Space Static Pressure
Sensor Value Not Valid
Auto
Informational
91
OA Filter Pressure
Sensor Value Not Valid
Auto
Informational
92
Supply Duct Stat Press Sensor Value Not Valid
Auto
Disable Static Press Control
93
Return Duct Stat Press Sensor Value Not Valid
Auto
Disable Static Press Control
94 - 97
Sup Fan (x) AFMS
Sensor Value Not Valid
Auto
Informational
98 - 101
Ret Fan (x) AFMS
Sensor Value Not Valid
Auto
Informational
102 -105
Exh Fan (x) AFMS
Sensor Value Not Valid
Auto
Informational
106
Min Outside Dmpr AFMS
Sensor Value Not Valid
Auto
Informational
107
Outside Damper AFMS
Sensor Value Not Valid
Auto
Informational
108
HW Exhaust Pressure
Sensor Value Not Valid
Auto
Disable Wheel Ex Bypass
Heat Wheel
109
HW Supply Pressure
Sensor Value Not Valid
Auto
Disable Wheel Ex Bypass
Heat Wheel
110 - 121
Zone (x) Space Temp
Sensor Value Not Valid
Auto
Disable Zone Control
122
Space Setpt Adj Slider
Sensor Value Not Valid
Auto
Informational
123
Space 2 CO2
Sensor Value Not Valid
Auto
Disable CO2
124
Return CO2
Sensor Value Not Valid
Auto
Disable CO2
125 - 132
Discharge Press Ckt (x) Sensor Value Not Valid
Auto
Disable Compressor Circuit
133 - 140
Suction Press Ckt (x)
Sensor Value Not Valid
Auto
Disable Compressor Circuit
Only with
EVD
141 - 148
Discharge Temp Ckt (x) Sensor Value Not Valid
Auto
Disable Compressor Circuit
Only with
EVD
149 - 156
Suction Temp Ckt (x)
Sensor Value Not Valid
Auto
Disable Compressor Circuit
Only with
EVD
157 - 164
High Disch Temp Ckt (x) Compressors Disabled
Auto
Disable Compressor Circuit
165 - 172
High Superheat Ckt (x)
Compressors Disabled
Manual
Disable Compressor Circuit
173 - 180
Low Superheat Ckt (x)
Auto
Disable Compressor Circuit
181 - 188
High Compression
Ckt (x) Comps Disabled Auto until Lockout 3x in 1 hr Disable Compressor Circuit
189 - 196
High Suction Pressure Ckt (x) Comps Disabled Auto until Lockout 3x in 1 hr Disable Compressor Circuit
197 - 204
Low Condenser Pressure Ckt (x) Comps Disabled Auto until Lockout 3x in 1 hr Disable Compressor Circuit
205 - 212
Ckt A High Saturated
Discharge Temperature
Auto
Disable Compressor Circuit
213 - 220
Ckt A Low Saturated
Suction Temperature
Auto
Disable Compressor Circuit
221
Supply Air Temperature
Low Limit Shutdown
Manual
Shutdown Unit
222
Heat Wheel Rotation
Not Detected
Auto
Informational
223 - 226
Slave Unit (x) Offline
Auto
Informational
227
Master Unit Offline
Auto
Disable Slave Mode
228 - 235
Ckt (x) Abnormal Press Compressors Disabled
Auto
Disable Compressor Circuit
236
Heat Pump Defrost
Mode is Active
Auto
3x in 1 hr
Informational
237
Multi Devices per Ch
Contact Unison
Auto
Informational
238 -239
Exp Board (x) Failure
Board is Offline
Auto
Shutdown Unit
240
Shutdown Contact
In Alarm Position
Auto
Shutdown Unit
241
Cold Deck Temperature Sensor Value Not Valid
Auto
Disable Cold Deck Control
242
Hot Deck Temperature
Sensor Value Not Valid
Auto
Disable Hot Deck Control
CONTROLLER
Alarm Data