100
Rooftop Dedicated Outdoor
Air System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 59:
BACnet and MODBUS Points List, continued.
Variable
Description
Active
Text
Inactive
Text
BACnet
MODBUS
Object
Instance
Object
Type
Access
Hyst Index Register
Type Size
Binary Values – Read Only, continued.
Leaving_Water_Temp_1_Alarm.
Active
Return Water
Temp Alarm
Alarm
Normal
534
BV
ReadCOV_NoWrite 0 10484 Discrete
Space_CO2_1_Analog_Input_
Alarm.Active
Space CO2 1
Analog Input
Alarm
Alarm
Normal
535
BV
ReadCOV_NoWrite 0 10485 Discrete
Space_High_Static_Alarm.
Active
Space High Static
Alarm
Alarm
Normal
537
BV
ReadCOV_NoWrite 0 10487 Discrete
Space_RH_Sensor_Alarm.
Active
Space RH Sensor
Alarm
Alarm
Normal
538
BV
ReadCOV_NoWrite 0 10488 Discrete
Space_Setpoint_Slider_Alarm.
Active
Space Setpoint
Slider Alarm
Alarm
Normal
539
BV
ReadCOV_NoWrite 0 10489 Discrete
Space_Static_Pressure_
Analog_Input_ Alarm.Active
Space Static
Pressure
Analog Input
Alarm
Alarm
Normal
540
BV
ReadCOV_NoWrite 0 10490 Discrete
Space_Temperature_Sensor_
Alarm.Active
Space
Temperature
Sensor Alarm
Alarm
Normal
541
BV
ReadCOV_NoWrite 0 10491 Discrete
Shutdown_Input_Alarm.Active
Shutdown Input
Alarm
Alarm
Normal
546
BV
ReadCOV_NoWrite 0 10496 Discrete
Supply_Air_Temp_Low_Limit.
Active
Supply Air Temp
Low Limit
Alarm
Alarm
Normal
551
BV
ReadCOV_NoWrite 0 10501 Discrete
Supply_Air_Temperature_
Sensor_Alarm. Active
Supply Air
Temperature
Sensor Alarm
Alarm
Normal
552
BV
ReadCOV_NoWrite 0 10502 Discrete
Supply_Duct_Static_Pressure_
Analog_ Input_Alarm.Active
Supply Duct Static
Pressure
Analog Input
Alarm
Alarm
Normal
553
BV
ReadCOV_NoWrite 0 10503 Discrete
Supply_Fan_1_Alarm.Active
Supply Fan 1
Alarm
Alarm
Normal
554
BV
ReadCOV_NoWrite 0 10504 Discrete
Supply_Fan_1_CFM_Analog_
Input_Alarm. Active
Supply Fan 1 CFM
Analog Input
Alarm
Alarm
Normal
558
BV
ReadCOV_NoWrite 0 10508 Discrete
Supply_High_Duct_Static_
Alarm.Active
Supply High Duct
Static Alarm
Alarm
Normal
563
BV
ReadCOV_NoWrite 0 10513 Discrete
Supply_RH_Sensor_Alarm.
Active
Supply RH Sensor
Alarm
Alarm
Normal
564
BV
ReadCOV_NoWrite 0 10514 Discrete
Supply_Temp_High_Limit_
Alarm.Active
Supply Temp High
Limit Alarm
Alarm
Normal
565
BV
ReadCOV_NoWrite 0 10515 Discrete
Entering_Water_Temp_1_Alarm.
Active
Entering Water
Temp Alarm
Alarm
Normal
566
BV
ReadCOV_NoWrite 0 10516 Discrete
TMem_Error.Active
TMem Error Alarm
Alarm
Normal
567
BV
ReadCOV_NoWrite 0 10517 Discrete
Wheel_Rotation_Alarm.Active
Wheel Rotation
Alarm
Alarm
Normal
576
BV
ReadCOV_NoWrite 0 10526 Discrete
Al_Batt_EVD_1.Active
EVD Battery Alarm Alarm
Normal
589
BV
ReadCOV_NoWrite 0 10539 Discrete
Al_ConfigErr_EVD_1.Active
EVD Configuration
Alarm
Alarm
Normal
590
BV
ReadCOV_NoWrite 0 10540 Discrete
CONTROLLER
BACnet and MODBUS Points