Device parameters and interfaces
Leuze electronic
BPS 34
75
TNT 35/7-24V
8.1.7.19 Module 18: Measuring error tolerance
Description
The measuring error tolerance function is used to configure a time which results in an
extended output of the last position value (module 1) in the event of an error. If the position
value changes momentarily to zero, e.g. due to a brief interruption of the laser beam, soiling
of the barcode tape or other short-term disturbances, the BPS transmits the last valid posi-
tion value.
If the error disappears within the configured time, the control notices nothing or only a small
change in the position value. The availability of the system is thereby ensured. No new
values are delivered by the BPS 34, however, for a period of time extending up to the config-
ured tolerance time. With the "delay error output" parameter, an integration error (corre-
sponds to a missing position value) can be signalled immediately or after the tolerance time
has elapsed. If the error persists after the tolerance time has elapsed, a position value of
zero is output.
Parameter
Hex coding of module 18 "Measuring error tolerance"
The value listed in the table shows the hex coding of the default settings.
Input data
none
Output data
none
Parameter
Description
Rel.
addr.
Data
type
Value range
Default
Unit
CR to
module
Position
tolerance
time in
[ms]
Specifies the time for the output
of the last position value follow-
ing an error
0
unsign
16
0 … 65’535
50
ms
–
Delay error
output
Delays the output of an integra-
tion error by the configured tol-
erance time.
2
unsign
8
0: No, error delay deactivated
1: Yes, error delay activated
1
–
–
Parameter length: 3 bytes
a
b
Internal ad
dress
of module 18
P
o
sition
tolerance time
ad
dress 0
Dela
y err
o
r output
ad
dress 2
14
00 32
01