Device parameters and interfaces
Leuze electronic
BPS 34
71
TNT 35/7-24V
8.1.7.15 Module 14: Static position limit value 1
Description
The limit value function compares the output position value with a position stored during
configuring. If the value is above or below the limit value, the limit value status 1 (module 12)
is set and, if configured, the switching output (module 8) is appropriately set.
Parameter
Hex coding of module 14 "Static position limit value 1"
The value listed in the table shows the hex coding of the default settings.
Input data
none
Output data
none
Notice!
With this module, the settings for the Preset (module 3), Offset (module 5) and Scaling
(module 6) modules must be taken into account.
Parameter
Description
Rel.
addr.
Data
type
Value range
Default
Unit
CR to
module
Limit value
mode 1
Parameter activates limit
value checking.
0
unsign
8
0: Off
1: On
0
–
7 g
Switching
mode 1
Condition for the signal
change of the switching out-
put/status bit.
1
unsign
8
0: Value greater than limit
1: Value less than limit
0
–
8d
Hysteresis 1
in [mm]
Relative offset of switching
point
2
unsign
16
0 … 65’535
0
mm
–
Limit value 1
in [mm]
Limit value is compared to the
current position value.
4
sign32 -10’000’000 … 10’000’000
0
mm
12e
Parameter length: 8 byte
a
b
c
d
Internal ad
dress
o
f modu
le 14
Limit v
a
lue mode 1
ad
dress 0
Switc
h
in
g mo
de 1
ad
dress 1
Hysteresis 1
ad
dress 2
Limit v
a
lue 1
ad
dress 4
0D
00
00
00 00
00 00 00 00