EtherNet/IP interface
Leuze electronic
AMS 358
i
66
TNT
35/7-2
4
V
9.7.2.9
Alarms
Attribute 44
The PLB and ERR status messages generated by AMS 358
i
are entered in bit 0 and bit 1.
The alarms entered here result in incorrect measurement values on the AMS 358
i
. The CIP
spec. distinguishes between alarms and warnings.
The following applies for PLB and ERR:
0 = no alarm
1 = alarm
9.7.2.10 Supported alarm
Attribute 45
Attribute 45 shows which alarms specified by the position sensor object are supported by
the AMS 358
i
.
Bit 0 =1; PLB alarm is supported by the AMS 358
i
.
Bit 1 =1; ERR alarm is supported by the AMS 358
i
.
Bit 2 to bit 15 = 0
9.7.2.11 Alarm flag
Attribute 46
The attribute evaluates the alarms supported in attribute 45 in an OR function. (Collective
alarm)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
reserved
ERR
PLB
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Vendor spec.
reserved
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
reserved
1
1
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Vendor spec.
reserved