Fast commissioning / operating principle
Leuze electronic
AMS 358
i
12
TNT
35/7-2
4
V
Activating parameter enabling
To be able to perform the subsequent address assignment, parameter enabling must first
be activated.
ª
To do this, select the
ON
menu item in the
Parameter -> Parameter handling ->
Parameter enable
menu.
Notice!
The display is inverted while parameter enabling is active.
Manually assigning network addresses of the AMS 358
i
In the display under the
EtherNet/IP
menu item, you will find the input masks for
• IP address,
• Network mask (subnet),
• Gateway address (provided a gateway exists).
ª
Enter the corresponding addresses.
Automatically assigning addresses via DHCP
Under the
EtherNet/IP
menu item, you will find the input mask for activating or deactivating
the DHCP functionality. DHCP address assignment is set to "OFF" by default.
ª
To activate DHCP, select
ON.
Provided the DHCP server supplies the corresponding addresses, the address fields for
IP address, network mask and gateway address are preset by the DHCP server.
Automatically assigning addresses via BOOTP
Under the
EtherNet/IP
menu item, you will find the input mask for activating or deactivating
the BootP functionality. BootP address assignment is set to "OFF" by default.
ª
To activate BootP, select
ON.
Provided the BootP server supplies the corresponding addresses, the address fields for
IP address, network mask and gateway address are preset by the BootP server.
Notice!
The data can be called up via the display in the main menu under
Network information
.
Deactivating parameter enabling
ª
To deactivate parameter enabling, select the
OFF
menu item in the
Parameter ->
Parameter handling -> Parameter enable
menu.
Configuring the participant (e.g., in the RSLogix 5000).
In the RSLogix 5000 configuration tool for EtherNet/IP, a so-called "Generic EtherNet
Module" is created for the AMS 358
i
under the "Communication" path.