Fast commissioning / operating principle
13
AMS 358
i
Leuze electronic
The input mask for the Generic Module describes:
• The name of the participant (can be selected freely; e.g., AMS358i_1).
• The format of the I/O data (Data - DINT = 32 bit).
• The IP address of the participant.
• The address and length of the input assembly (instance 1; 1 x 32 bit for the default input
assembly of the measured-value data).
• The address and length of the output assembly (instance 120; 2 x 32 bit for the default
output assembly).
• Optional: The address and length of the configuration assembly (instance 190;
102 x 8 bit).
Attention!
If the configuration assembly is addressed with instance 190 and length 102 in the input mask
for the generic module, all AMS 358
i
parameters with the value 0 are occupied in the first
moment. All default parameters of the AMS manual must be entered in the configuration
assembly. Changing the individual default values is possible at any time.
For the exact description of the assemblies for input/output and configuration, please refer
to chapter 9.7.
The query cycle of the input and output assemblies is subsequently defined in the "Module
Properties - Connection" path in the "Request Packet interval (RPI)" input field.
The participant is thereby defined in offline mode; the data must subsequently be transferred
to the control.
Transfer the data to the control (RSLogix 5000 specific)
ª
Activate online mode.
ª
Select the EtherNet communication port.
ª
Select the processor onto which the project is to be transferred.
ª
Set the control to "PROG".
ª
Start the download.
ª
Set the control to "RUN".
Configure the config assembly
The AMS 358
i
makes available a configuration assembly that allows the entire parameter
set of the AMS 358
i
to be saved in the control and, if necessary, to be called up.
The config assembly must include all parameters that affect the AMS 358
i
. The config
assembly is automatically written to the connected participants in cycles that the control
manufacturer defines.
The config assembly is implemented in class 4, under instance 190. By default, all
parameters are preset to the value 0 (zero).