E94AYCCA communication manual (CANopen®)
Commissioning
Possible settings via DIP switches
34
L
EDS94AYCCA EN 5.0 - 06/2012
6.2.2
Setting the baud rate
The baud rate can be set with the DIP switches
a ... d
or via the »Engineer« (code
/
If several CAN nodes are interconnected, their baud rates must be identical.
Tip!
The baud rate resulting from the DIP switch setting applied at last mains power-up
/
.
Switch positions
Baud rate
d
c
b
a
OFF
ON
ON
OFF
10 kbps
OFF
ON
OFF
ON
20 kbps
OFF
OFF
ON
ON
50 kbps
OFF
OFF
ON
OFF
125 kbps
OFF
OFF
OFF
ON
250 kbps
OFF
OFF
OFF
OFF
500 kbps
ON
ON
ON
OFF
800 kbps
OFF
ON
OFF
OFF
1000 kbps
OFF
ON
ON
ON
Automatic detection
Note!
Switch the voltage supply of the standard device off and then on again to
activate altered settings.