EDS94AYCCA EN 5.0 - 06/2012
L
33
E94AYCCA communication manual (CANopen®)
Commissioning
Possible settings via DIP switches
6.2
Possible settings via DIP switches
[6-1]
DIP switch
6.2.1
Setting the node address
If several CAN nodes are interconnected, their node addresses must differ from each
other.
The node address can be set with the DIP switches
1 ... 64
or via the »Engineer« (code
/
Valid address range: 1 … 127
The labelling on the package corresponds to the values of the individual DIP switches for
determining the node address.
Tip!
The node address resulting from the DIP switch setting applied at last mains
power-up is indicated under
.
9400CAN003
The front DIP switches can be used to set:
address (switches 1 ... 64)
baud rate (switches a ... d)
Lenze setting: all switches OFF
Baud
CAN Address
O
N
c
d
b
a
64
32
16
8
4
2
1
Baud
CAN Address
O
N
c
d
b
a
64
32
16
8
4
2
1
Baud
CAN Address
O
N
c
d
b
a
64
32
16
8
4
2
1
Node address determined by ...
DIP switch
C13350 / 14350
Prerequisite
At least one switch
1 … 64 = ON
Switches
1 ... 64 = OFF
DIP switch
64
32
16
8
4
2
1
Switch position
OFF
OFF
ON
OFF
ON
ON
ON
Value
0
0
16
0
4
2
1
Node address
= Sum of the values = 16 + 4 + 2 + 1 = 23
DIP switch positions for setting the CAN node address (
Note!
Switch the voltage supply of the communication module off and then on again
to activate altered settings.