E94AYCCA communication manual (CANopen®)
Parameter reference
Parameters of the communication module for slot MXI2
134
L
EDS94AYCCA EN 5.0 - 06/2012
C14347
C14348
C14349
Parameter | Name:
C14347 | CAN heartbeat status
Data type: UNSIGNED_8
Index: 11228
d
= 2BDC
h
Status of node 1 ... 32
Selection list
(read only)
0 Unknown
4 Stopped
5 Operational
127 Pre-operational
Subcodes
Information
C14347/1
...
C14347/32
;
Read access
Write access
CINH
PLC STOP
No transfer
Scaling factor: 1
Parameter | Name:
C14348 | CAN status DIP switch
Data type: UNSIGNED_8
Index: 11227
d
= 2BDB
h
• The value "1" means that the CAN DIP switches have been recognised during power-on and a valid baud rate and
node address have been set.
• The value "0" means that either no CAN DIP switch or no valid setting has been recognised or that the setting has
been overwritten by code
.
Selection list
(read only)
Information
0 Setting not accepted
1 Setting accepted
;
Read access
Write access
CINH
PLC STOP
No transfer
Scaling factor: 1
Parameter | Name:
C14349 | CAN setting of DIP switch
Data type: UNSIGNED_8
Index: 11226
d
= 2BDA
h
CAN DIP switch setting during last power-on
Possible settings via DIP switches (
Display range
(min. value | unit | max. value)
0
255
Subcodes
Information
C14349/1
Node address
C14349/2
Baud rate:
0: 500 kbps
1: 250 kbps
2: 125 kbps
3: 50 kbps
4: 1 Mbps
5: 20 kbps
6: 10 kbit/s
14: 800 kbps
255: Automatic detection
;
Read access
Write access
CINH
PLC STOP
No transfer
Scaling factor: 1