FSoE parameter
Parameter
Unit
Safety module
Setting / range
[Default]
Description / note
Input x filter time [µs]
µs
SDI16/SDO4 and SDI16
Input 0 filter time [µs] - Input 15
filter time [µs]
500 ... 1500
[1500]
SDI8/SDO2
Input 0 filter time [µs] - Input 7 fil-
ter time [µs]
500 ... 1500
[1500]
Test pulse length of input x
Input filter of input x
The digital test pulse output is interrupted for the set duration of every test
pulse. The Safety I/O-module checks whether the digital inputs may turn Null
and whether there are any short circuits to noise voltages on the signal line.
Adapt the test pulse duration to the peripherals you use.