Configuration
Attention
Check the safety function
Potential faults due to maladjusted configuration
After initial installation and after replacing a module, check the safety
function!
6.3.1
Address Setup
c250-S Safety has a safe module address (FSoE slave address) which clearly identifies it in the
safe communication network. The address is set manually by means of binary switches on the
left side of the module.
Use the 2x 8 DIP switches to set the FSoE address. Addresses range between 1 and 65535.
Information
After setting the FSoE address, disconnect the c250-S Safety module once from
the power supply to ensure that the address is accepted and a module test
started automatically.
Information
There is no access to the DIP switches once several modules have been lined up.
To set the FSoE slave address at the DIP switch, first remove the module from
the row of modules.