FSoE parameter
Parameter
Unit
Range
[Default]
Description / note
usedOutputs
Dec
00
2
.... 11
2
[00
2
]
Enables the outputs you use (0 and / or 1)
Selection from a drop-down list depends on the configurator
00 outputs disabled
01 SO 0 enabled, SO 1 disabled
10 SO 0 disabled, SO 1 enabled
11 SO 0 enabled, SO 1 enabled
extGroundOutputs
Dec
00
2
.... 11
2
[00
2
]
Enable if the actuator is not connected to module terminal SO X- but uses an
external ground connection.
Selection from a drop-down list depends on the configurator
Test pulse duration input 0
µs
300 ... 1500
[500]
Test pulse length of input 0
Input filter of input 0
The digital test pulse output is interrupted for the set duration of every test
pulse. The Safety I/O-module checks whether the digital inputs may turn Null
and whether there are any short circuits to noise voltages on the signal line.
Adapt the test pulse duration to the peripherals you use.
Test pulse duration input 1
µs
300 ... 1500
[500]
Test pulse length of input 1
Input filter of input 1
The digital test pulse output is interrupted for the set duration of every test
pulse. The Safety I/O-module checks whether the digital inputs may turn Null
and whether there are any short circuits to noise voltages on the signal line.
Adapt the test pulse duration to the peripherals you use.