6
Installation and Operation
EDBC250SIO | 2.0
67
FSoE parameter
Parameter
Unit
Range
[Default]
Description / note
Bits 6,7
00
2
… 11
2
[00
2
]
Pressure-sensitive mat / bumper, bits 6 & 7
00 disabled
01 inputs 0 & 1
10 inputs 2 & 3
11 inputs 0 & 1 and inputs 2 & 3
Bit
Decim
al
Setting
7 6 5 4 3 2 1 0
0 0 0 0 0 0 0 0 0
No function
0 0 0 0 0 0 0 1 1
Test pulse output of input 0 disabled
0 0 0 0 0 0 1 0 2
Test pulse output of input 1 disabled
0 0 0 0 0 1 0 0 4
Test pulse output of input 2 disabled
0 0 0 0 1 0 0 0 8
Test pulse output of input 3 disabled
0 0 0 0 1 1 1 1 15
All test pulse outputs of all inputs disabled
0 0 0 1 0 0 0 0 16
Mode selector, two channels (inputs 0 + 1)
0 0 1 0 0 0 0 0 32
Mode selector, three channels (inputs 0 - 2)
0 0 1 1 0 0 0 0 48
Mode selector, four channels (inputs 0 - 3)
0 1 0 0 0 0 0 0 64
Pressure-sensitive mat, inputs 0 + 1
1 0 0 0 0 0 0 0 128
Pressure-sensitive mat, inputs 2 + 3
1 1 0 0 0 0 0 0 192
Pressure-sensitive mat, inputs 0 + 1 and 2 + 3
Red cells:
•
In mode selector or pressure-sensitive mat modes, disabling a test pulse output will provoke an error message
•
Settings in red cells are therefore forbidden
Green cells:
•
Pressure-sensitive mat mode available for inputs 0+1 or 2+3
•
Mode selector mode available for inputs 0+1, 0-2 or 0-3
Blue cells:
•
Test pulse outputs can be disabled
Example:
Assuming you wish to run a pressure-sensitive mat at inputs 0&1 of the Safety I/O-module while disabling the test
pulses of the other inputs (2&3). Set up as follows:
64 + 4 + 8 = 76