User manual of ELP AC Servo
www.leadshine.com
73
Repower
-
Pr6.09
Name
Negative torque compensation
value
Mode
P
S
T
Range
-100~100
Unit
%
Default
0
Data Type
16bit
Access
R/W
Address
0613H
Repower
-
This three parameters may apply feed forward torque superposition directly to torque
command.
Pr6.13
Name
2
nd
inertia ratio
Mode
P
S
T
Range
0~10000
Unit
%
Default
0
Data Type
16bit
Access
R/W
Address
061BH
Repower
-
Set up 2
nd
inertia ratio
Set up the ratio of the load inertia against the rotor of the motor ratio.
PR6.13= ( load inertia/ rotor inertia ) * 100
【
%
】
Pr6.14
Name
Emergency stop time at alarm
Mode
P
S
T
Range
0~3000
Unit
ms
Default
200
Data Type
16bit
Access
R/W
Address
061DH
Repower
-
Set up the time allowed to complete emergency stop in an alarm condition, exceeding
this time puts this system in alarm state.
Pr6.20
Name
Trial run distance
Mode
P
Range
0~1200
Unit
0.1rev
Default
10
Data Type
16bit
Access
R/W
Address
0629H
Repower
-
The distance of running each time in JOG run(position control)
Pr6.21
Name
Trial run waiting time
Mode
P
Range
0~30000
Unit
Ms
Default
100
Data Type
16bit
Access
R/W
Address
062BH
Repower
-
The waiting time after running each time in JOG run(position control)