Chapter 4 Hardware Installation
- 23 -
the outlet part of cable channel or at turnings should be bundled and fixed.
8
.
If cables, power line and grounding conductor are laid in the same channel,
cables, power line and grounding conductor should be not folded or blended
together. If a cable line is overly long, coil and place it in the middle of the
cabling rack, do not let it cover on other cables.
9
.
When laying the pigtail, avoid knotting of optical fiber cable, minimize the
amount of turnings and avoid turnings with overly small radius. Bundle
pigtails in proper tightness and avoid too tightly bundling. If laid on a cabling
rack, it should be placed separately from other cables.
10. There must be the relevant marks at both ends of cable and the information on
the marks should be explicit to facilitate maintenance
Attention: When laying pigtails, prevent optical fiber cable from knotting, minimize the
amount of turnings and avoid turnings with too small radius, because turning with too small radius
will result in serious consumption of optical signal of links, affecting communication quality.