3.6.12
CONNECTING THE SIGNAL FOR PV SIGNAL
NOTE
Connect the PV signal in case you have a combination of PV collectors and a
heat pump. Set the controller for the desired function when the signal is present.
NOTE
The PV signal and remote switch between heating / cooling cannot be
connected at the same time.
Connect the PV signal to serial clamp X4,
connect it to D8 and GND.
The signal must be short-circuited and
potential-free.
3.6.13
CONNECTING THE SIGNAL FOR REMOTE OFF
NOTE
Connect the signal for remote off in case the heating system is controlled by an
external controller.
Connect the signal for remote switch to serial
clamp X4, connect it to D5 and GND.
The signal must be short-circuited and
potential-free.
3.7 Commissioning of the device
After professional installation, the authorised contractor for commissioning has to perform
the commissioning of the device.
CAUTION
The commission can only be performed by a person authorised by the
manufacturer! If the commission is performed by an unauthorised person, the
warranty is not recognised.
CAUTION
Before commissioning, it is necessary to perform all the required tasks and
inspections from the tasks for commission.