The minimal volume of the buffer tank V
min
= 11 kW x 15 L/kW = 165 L
Picture 13: Scheme of a system with several heating cycles, buffer tank and DHW buffer tank
3.5.3.3 Bivalent system
A bivalent system uses an additional heat generator in addition to the heat pump to heat
the building.
Set up the bivalent system in accordance with the schemes below.