Roof Pitch
H (Min.) Ft. H (Min.) m
Flat to 6/12
1.0
0.30
Over 6/12 to 7/12
1.25
0.38
Over 7/12 to 8/12
1.5
0.46
Over 8/12 to 9/12
2.0
0.61
Over 9/12 to 10/12
2.5
0.76
Over 10/12 to 11/12
3.25
0.99
Over 11/12 to 12/12
4.0
1.22
Over 12/12 to 14/12
5.0
1.52
Over 14/12 to 16/12
6.0
1.83
Over 16/12 to 18/12
7.0
2.13
Over 18/12 to 20/12
7.5
2.27
Over 20/12 to 21/12
8.0
2.44
H
12
X
ROOF PITCH = X/12
H (minimum)
- MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
APPROVED CAP
APPROVED VENT PIPE
DISCHARGE OPENING
*8' MIN
*
- IF VENT IS CLOSER THAN 8', IT MUST
TERMINATE AT LEAST 2' HIGHER THAN ANY
PORTION OF A BUILDING WITHIN 10' OF THE VENT
VENT TERMINATION CLEARANCES
CAUTION: This appliance must
not be connected to or joined
with any chimney flue serving
any other appliance.
VENTING
(Vertical Cap Requirements)
*(2.44 m)
*
IF VENT IS CLOSER THAN 8’ (2.44 m), IT MUST TERMINATE AT
LEAST 2’ (0.61 m) HIGHER THAN ANY PORTION OF A BUILDING
WITHIN 10’ (3.05 m) OF THE VENT.
PAGE 36
Summary of Contents for Dassel DSL-36-RF
Page 68: ...PAGE 67...
Page 69: ...PAGE 68...