VENTING
(Horizontal & Vertical Combination)
CAUTION: This gas
appliance must not be
connected to or joined
with any other chimney
flue serving another
appliance.
NOTE: Horizontal
sections require
1/4” (6 mm) rise for
every 12” (305 mm)
of travel.
PAGE 32
Depending on your
particular venting
needs, a Decreaser
may be necessary to
terminate the venting
system.
IMPORTANT: A WALL THIMBLE PASS-THRU MUST BE USED ON ALL HORIZONTAL VENT
RUNS THAT PASS THROUGH EITHER INTERIOR OR EXTERIOR WALLS.
IF USING 5” x 8” VENTING, USE KOZY HEAT WALL THIMBLE PASS-THRU (#800-WPT)
FOLLOW INSTRUCTIONS ON PAGE 23 OF THIS INSTALLATION MANUAL.
IF USING A 8” x 6-5/8” DECREASER, FOLLOW VENT PIPE MANUFACTURER‟S
INSTALLATION INSTRUCTIONS FOR THEIR WALL THIMBLE.
For each additional 90
˚
elbow used after the first elbow, 3 ft. (91
4 mm) must be subtracted from the maximum venting allowed.
For each 45° elbow used, 1-1/2 ft. (457 mm) must be subtracted from the maximum venting allowed.
NOTE: (2) 45° degree elbows may be used in place of (1) 90° elbow.
IMPORTANT: THE HORIZONTAL VENT HEAT SHIELD INCLUDED WITH THIS FIREPLACE
MUST BE INSTALLED WHEN USING A 90° ELBOW DIRECTLY OFF THE UNIT TO
HORIZONTALLY POSITION THE VENT SYSTEM. THIS INCLUDES ANY CORNER
INSTALLATION.
TERMINATION MUST BE
WITHIN SHADED AREA.
HORIZONTAL / VERTICAL
COMBINATION
20‟ (6.10 m) VERTICAL
20‟ (6.10 m) HORIZONTAL
NOTE: Pages 28-29
have information on
restrictor installation
in conjunction with
venting installation.
Page 57 has information on
Restrictor recommendations
depending on burner flame
appearance and instructions on
installation after venting is
completed.