VENTING
(Horizontal)
90
°
ELBOW
NOTE: Horizontal sections
require 1/4” (6 mm) rise for
every 12” (305 mm) of travel.
IMPORTANT: A WALL THIMBLE PASS-THRU
MUST BE USED ON ALL HORIZONTAL VENT
RUNS. IF USING A 8” x 6-5/8” DECREASER
FOLLOW VENT PIPE MANUFACTURER‟S
INSTALLATION INSTRUCTIONS FOR THEIR
WALL THIMBLE.
MAXIMUM HORIZONTAL VENTING
WITH 8” x 6-5/8” DECREASER
HORIZONTAL TERMINATIONS
CAUTION: This gas
appliance must not be
connected to or joined with
any other chimney flue
serving another appliance.
IMPORTANT:
Depending on your
particular venting
needs, a Decreaser
may be necessary to
terminate the venting
system.
PAGE 27
6”
(152 mm)
2 FT
(610 mm)
MAXIMUM HORIZONTAL VENTING
25 ft. (7.62 m) maximum, or 30 ft (9.14 m) maximum when
using stainless steel pipe for the entire length of termination.
2 FT
(610 mm)
TERMINATION CAP
90
°
ELBOW
8” x 6-5/8” DECREASER
8” x 6-5/8” DECREASER
TERMINATION CAP
NOTE: Pages 28-29 have information
on restrictor installation in
conjunction with venting installation.
Page 57 has information on restrictor
recommendations depending on
burner flame appearance and
instructions on installation after
venting is completed.
MINIMUM HORIZONTAL VENTING
WITH 8” x 6-5/8” DECREASER