451253/A
19
Requirements for insulation, heating and ventilation
The bulkheads in the sonar room should be insulated and provided with an interior wall
to the deck. The room should be equipped with heater and connected to the vessel's
ventilation system.
Heating requirements
Heating is an effective method for reducing humidity. The heater in the sonar room must
be dimensioned to maintain the equipment within its environmental tolerances.
Observe the environmental specifications related to the SBP 29 units.
Ventilation requirements
The sonar room should be connected to the vessel's ventilation system to ensure a supply
of cooling air. If a ventilation system is not available, install two 3” pipes from the sonar
room to a suitable fresh air location on deck.
The fresh air should enter the room as close to the floor as possible, and should be
extracted from as high as possible. A funnel shaped drip-collector must be mounted
below the vent pipes to divert moisture to the bilge. On the main deck, the best
ventilation is provided when the outlet pipe is at least four meters higher than the inlet
pipe. To keep out sea water, rain and spray, the ventilation pipes must be fitted with
goosenecks or an equivalent design.
Note
If the vessel is likely to operate in tropical conditions, a suitable air conditioning system
must be installed. The air conditioning system must be able to provide an ambient
temperature that does not exceed the maximum operating temperatures of the SBP 29
units that are installed in the room.
Requirements for electrical installations, cables and
communication
The electrical installations in the sonar room must meet minimum requirements to
provide suitable lights and supply power.
Light requirements
The sonar room must be equipped with suitable lighting to simplify the installation
and to aid future maintenance.
Communication requirements
The sonar room should be equipped with a telephone, an intercom system, or any other
means of oral communication between the sonar room and the bridge and/or control
room(s).
Summary of Contents for SBP 29
Page 1: ...451253 A November 2019 Kongsberg Maritime AS SBP 29 Sub bottom profiler Installation Manual ...
Page 111: ...451253 A 111 Figure 12 862 216859 Drawing files ...
Page 112: ...112 451253 A Figure 13 307904 SBP 29 Installation Manual ...
Page 113: ...451253 A 113 Figure 14 862 218001 Drawing files ...
Page 114: ...114 451253 A Figure 15 871 219193 SBP 29 Installation Manual ...
Page 115: ...451253 A 115 Figure 16 871 219201 Drawing files ...
Page 116: ...116 451253 A Figure 17 388168 SBP 29 Installation Manual ...
Page 117: ...451253 A 117 Figure 18 871 219187 Drawing files ...
Page 118: ...118 451253 A Figure 19 821 219199 SBP 29 Installation Manual ...
Page 119: ...451253 A 119 Figure 20 388235 Drawing files ...
Page 120: ...120 451253 A Figure 21 871 219198 SBP 29 Installation Manual ...
Page 121: ...451253 A 121 Figure 22 388148 Drawing files ...
Page 122: ...122 451253 A Figure 23 315550 SBP 29 Installation Manual ...
Page 123: ...451253 A 123 Figure 24 430751 Drawing files ...
Page 124: ...124 451253 A Figure 25 871 212984 SBP 29 Installation Manual ...
Page 125: ...451253 A 125 Figure 26 407070 Drawing files ...
Page 126: ...126 451253 A Figure 27 448231_1A SBP 29 Installation Manual ...
Page 127: ...451253 A 127 Figure 28 427512 Drawing files ...
Page 128: ...128 451253 A Figure 29 435680 SBP 29 Installation Manual ...
Page 129: ...451253 A 129 Figure 30 444783 Drawing files ...
Page 151: ......
Page 152: ... 2019 Kongsberg Maritime ...