IDN 169 Edge selection
IDN 509 Extended edge selection
Bit
Meaning
Bit
Meaning
0
Latch 1 positive edge
0-4
Unused
1
Latch 1 negative edge
5
Continuous measurement Latch 1
2
Latch 2 positive edge
6
Continuous measurement Latch 2
3
Latch 2 negative edge
7
Unused
4-7
Unused
8
Latch 1 extended difference Enable
8
Auto-activation bit is not
supported
9/10
00 - negative -> negative
01 - negative -> positive
10 - positive -> negative
11 - positive -> positive
9-15
Unused
11
Latch 2 extended difference Enable
12/13
00 - negativ -> negativ
01 - negativ -> positiv
10 - positiv -> negativ
11 - positiv -> positiv
14/15 Unused
l
In continuous measurement, it is possible for multiple latch events to occur within
one sercos
®
cycle. In this case, the counter (status IDN 409-411) is incremented and
only the last event is stored as a value in IDN 130-134!
l
If a measuring window is required, this must be defined
before
it is configured in IDN
509, otherwise an error message is issued.
l
There are some differences in the inputs between S300 and S400/S600
S300:
digital 1 -> IDN 130,131; digital 2 -> IDN 132,133
S400/S600:
digital 2 -> IDN 130,131; digital 1 -> IDN 132,133
l
The measurement sensor release (IDN 405 & 406 or P-IDN 3038) must take place
after the start of the command (IDN 170)!
l
When the command 170 is active, IDN 169+509 cannot be changed.
Examples:
a)
Input 1 only, but both edges
Phase 2:
P-IDN 3000 26
Digital input 1 as latch
Phase 2/3/4:IDN 179
0x03
both edges active
Phase 4:
IDN 170
3
Start command
IDN 405
1
Probe release
The entered values are in IDN 130 + 131.
b)
Both inputs, all edges, 2 input extended difference positive to negative
Phase 2:
P-IDN 3000 26
Digital input 1 as latch
P-IDN 3001 26
Digital input 2 as latch
Phase 2/3/4:IDN 179
0x0F
all edges active
IDN 509
0x1800
measurement difference positive -> negative Input
2
Phase 4:
IDN 170
3
Start command
IDN 405
1
Probe 1 release
IDN 406
1
Probe 2 release
Information whether one or more events have already been recorded is found in:
l
IDN 179 Bits 0+1 for input 1 and Bit 7 (0x0080) for the extended difference.
The individual statuses are, of course, also available.
The recorded values are in:
l
IDN 130 + 131 for input 1 and in IDN 523 for the extended difference