Connector Pinout And Descriptions
4/13/2012
Kollmorgen
32
S200 Position Node Installation Guide
Recommended Mating Connectors:
Spring Fork Lugs or M4 or #8 screws
Hollingsworth SS20948SF
Molex 19099-032
Or Equivalent
For maximum line droop tolerance connect logic power to 230Vac
instead of 115Vac
WARNING
After powering down the drive, monitor the BUS voltage by
connecting a meter from TB1-7 (+BUS) to TB1-6 (-BUS) to verify
the internal BUS capacitors have discharged prior to working on
the drive.
WARNING
The Regen input is not short circuit protected. The Regen
Resistance MUST be within specified ranges to prevent damage to
the drive. 15 Ohms minimum resistance for the S21260-xNS.
WARNING
Selected Regen Resistor must be able to handle constant 390Vdc
connection without risk of fire or must otherwise be thermally
protected with an overload device.
WARNING
Do not apply power or operate unit without the terminal block cover in
place.
N O TE