The discharge time for the bus capacitors may be as long as 5 minutes. After disconnecting the
drive from the ac mains be sure to wait 5 minutes before removing the drive’s cover and exposing
live parts.
The finished installation shall comply with the requirements of the IEC 364-4-41 series of
standards.
The cables and leads (except the protective conductors) used in the erection of the S200 in an
installation which are accessible for contact without opening or removing a barrier or are laid on
extraneous conductive parts shall have double or reinforced insulation between the core and the
surface or shall be surrounded by a metal screen having a satisfactory current-carrying capacity
in the event of a short-circuit between the core and the screen.
When installing the S200 into its operating location, it shall be ensured that any existing protective
separation according to 5.2.18 of EN50178 is maintained throughout the entire length of the
circuit in question. In installations the compliance for of the measures for protective separation
shall be checked by visual inspection.
Refer to Sections 1 and 4 of this manual for external fusing information.
Motor cable shield must be connected to protective earth.
During periods of extreme regeneration or excessively high input voltage the temperature of the
regen resistor may exceed 70 °C.
When using an external regen resistor, if regen cabling is accessible during normal machine
operation, regen resistor cable should be rated at 450 VDC and shielded with shield connected
to PE.
Consult the factory before using this product on a circuit protected by a residual-current-
operated protective device (RCD).
All covers shall be closed during operation.
The S200 drives should be used within their specified ratings.