Connector Pinout And Descriptions
4/13/2012
Kollmorgen
28
S200 Position Node Installation Guide
7.2 J1 –
L
OW
P
OWER
AC I
NPUT
P
OWER
M
ODELS
D
RIVE
P
OWER
Models S202x60-xNS, S203x0-xNS, S206x0-xNS
The S200 AC input drives are capable of direct line operation. All units are fully isolated and do not require
external isolation transformers. The inrush current on the connection to the line is internally limited to a safe level
for the drive. There are no voltage selection or ranging switches required to operate within the specified voltage
input ranges. Please note warnings that follow.
The S200 series drives are functionally compatible with all standard forms of three phase AC lines:
Grounded neutral WYE
Open-Delta Grounded Leg
TEE
1
9
Figure 7.1: J1 Connector view from front of drive
Pin
Description
J1-1
PE (Protective Earth) – Must be tied back to central earth bar.
J1-2
REGEN – Connection for optional external regen resistor.
J1-3
-BUS DC – Internal DC Bus negative connection (Not normally used)
J1-4
+BUS – Internal DC Bus Positive Connection (Regen Resistor
Termination Point)
J1-5
C2 CTRL VAC – Logic control Power can be tied to 120 or 230Vac input
J1-6
C1 CTRL VAC – Logic Control Power can be tied to 120 or 230Vac input
J1-7
L3 240 VAC – Main Line for Bus power: Used for 3
rd
Phase
J1-8
L2 240/120 VAC – Main Line for Bus Power. Used for 1 or 3 Phase
J1-9
L1 240/120 VAC – Main Line. Used for 1 or 3 Phase
Please refer to the Specifications Section for appropriate rating and fusing requirements
.
NOTE
It is the customer’s responsibility to supply appropriate fuses or circuit
breakers in the J1 AC drive power lines to comply with local electrical codes.