Termination
It is imperative that the vent termination be located observing the minimum clearances as shown.
There must not be any obstruction such as bushes, garden sheds, fences, decks or utility build-
ings within 24" from the front of the termination plate.
Do not locate termination where excessive snow or ice build-up may occur. Be sure to check vent
termination area after snow falls and clear to prevent accidental blockage of venting system. When
using snow blowers, make sure snow is not directed towards vent termination area.
General Venting Information
This gas appliance is approved to be vented either through the side wall or vertically through the roof.
Only Kingsman Flex(Z-Flex)Venting Kits and components specifically approved and LABELED for this
stove may be used.
This appliance is also approved for use with Simpson-Duravent Direct Vent system
(Model DV-
Pro
Series), Ameri-Vent Direct Vent Pipe System, ICC Excel Direct, Metal Fab Sure-Seal DV
and Selkirk Direct Temp.
Rigid or Hard Pipe
When using Simpson Duravent, AmeriVent pipe, ICC Excel Direct, Metal Fab Sure-Seal DV and or Selkirk
Direct Temp a Duravent hardpipe adapter must be used (
part # ZDVDFA for fireplaces and part # ZDVDKA for
Stoves, Serenity and ZDV3624B
). Follow installation instructions provided by Simpson
Duravent/AmeriVent/Selkirk Direct Temp, ICC Excel Direct, Metal Fab Sure-Seal DV for installation of pipe and
adhere to the clearance to combustibles provided in this manual. Apply a bead of Mill Pac high temp sealant to all
joints of pipes, adapters and termination, when using Kingsman Flex(Z-Flex)Venting venting and Simpson
Duravent venting.
NOTE: Increase framing depth by one inch when using hardpipe.
Minimum clearance to combustibles on venting is 1" [2.5cm] with the following exceptions:
Top of horizontal is 1-1/2" [3.8cm].
Top of 90 degree elbow in an enclosure over 44" [112cm] is 2-1/2" [6.4cm].
Venting terminal shall not be recessed into a wall or siding.
Venting Routes and Components
Since it is very important that the vent system maintain its balance between the combustion air
intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be
strictly adhered to. The table (see Horizontal Vent Table) showing the relationship
between vertical and horizontal side wall venting will help to determine the various vent lengths.
The maximum horizontal run with the 90 degree bend at the fireplace flue outlet is 4ft [122cm]
(see Figure 24). The maximum horizontal run is 20ft [6.1m] when the vertical run is 7ft [2.1m] (see
Figure 23). Note: 1/4" vertical rise is required for every 12" of horizontal run.
The maximum number of 45 degree bends per side wall installation is two [2] in the horizontal run
and then you must reduce the length of the horizontal by 18" for each 45 degree bend.
The maximum vertical run is 40ft [12.2m].
Special Note: For each 45 degree bend installed in the horizontal run, the length of the hori-
zontal run must be reduced by 18" [46cm]. This does not apply if the 45 degree bends are
installed on the vertical part of the vent system.
Example
If the length of the horizontal run is 10ft [3m], and two 45 degree bends are required, then the
horizontal run length must be reduced to 7ft to achieve proper venting. If 10ft of horizontal run is
required in conjunction with the two 45 degree bends, then the vertical run must be reduced
appropriately. Please refer to
the Horizontal Vent Table.
Note that two additional 90 degree bends, or equivalent, are allowed. However, to do so the hori-
zontal run must be reduced by 36" [91cm] for each 90 degree bend.
IMPORTANT: Always locate the fireplace in such a way that a minimum of offsets and/or hori-
zontal runs are required. 1/4” vertical rise is required for every 12” horizontal run.
38
Summary of Contents for Marquis Serenity MQZDV1917
Page 10: ...General Framing Installations Figure 5 General framing installation 10...
Page 31: ...Gas Conversion for Modulator PART C WARNING WARNING 31...
Page 34: ...Configuration 1 Basic manual HI LO and manual ON OFF capabilities 34...
Page 35: ...Receiver Module 584 523 521 221 1001 P221SI Receiver Module 584 523 521 221 1001 P221SI 35...