7. Testing and commissioning
Once the programming setup has been completed, verify that:
- the motors turn off after a few seconds once the opening or
closing phases end (also ERROR led turns OFF);
- the control unit responds to the connected wired commands:
START, pedestrian opening and STOP;
- all programmed radio transmitters are operational;
- the devices connected to PHO1 intervene while the gate
closes and prevent the open gate from closing;
- the devices connected to PHO2 intervene while the gate
opens and prevent the closed gate from opening;
If the PHO2 dip-switch is put to ON, check that they intervene
also when the gate closes and that they prevent the opened gate
from closing.
8. LEDs indication
1
2
3
4
5
6
7
8
ER
ROR
ST
OP
PH
O
TO
ST
A
RT
RADIO SE
T
8.1 - Input status indication LEDs
The following signals refer to the standby mode (that occurs 12
seconds after power up and inactivity).
PHOTO LED:
- ON in RED color if the PHO1 and PHO2 contacts are closed
- ON in GREEN color if the PHO1 contact is open
- ON in ORANGE color if the PHO2 contact is open
- OFF if the PHO1 and PHO2 contacts are open
GREEN STOP LED:
- ON if the STOP contact is closed
- OFF if the STOP contact is open
GREEN START LED:
- ON if the START contact is closed
- OFF if the START contact is open
RED RADIO LED:
- flashes when a command is received through King Gates
transmitter
- is OFF when the control unit is in standby mode
8.2 - Error status LED
RED ERROR LED:
The red
ERROR
LED has two functions:
•
The red ERROR LED flashes during the automation
movement when a mechanical stress point is detected
(this corresponds to increased motor effort). During
travel, only occasional led ERROR flashes are normal.
If led ERROR flashes for longer times, adjust OBS knob
(slightly turn it clockwise). Check gate mechanics if LED
ERR flashing continues.
• In standby mode, the LED shows the current error type with a
series of regular ashes according to the following scheme:
Flashes
per series
Error description
1
On-board memory fault
2
Photo-test failed.
See Paragraph 15.1 (advanced programmig
manual) for solving the problem
3
Gate travel path programming required.
See Paragraph 6
4
Input PHO2 set as a resistive edge and check
failed.
See Paragraph 15.3 (advanced programmig
manual) for solving the problem
GREEN START LED:
When START is activated by pressing the button or by wire
command, the LED flashes three times without gate movement.
this indicates that the “wire inputs” are in lock mode. To modify,
see par. 16.2 (advanced programming manual).
GREEN LED START, RED RADIO AND YELLOW SET:
If, when attempting to enter into any programming scheme, the
SET, RADIO and START LEDs flash fast three times, it means that
the “control unit protection” is activated. See Paragraph 17.1 for
solving the problem.
9. RESET procedure
Reset procedure deletes gate travel parameters (par. 6) and all
advanced functions (par. 11). It can be performed in case of
programming mistakes and it brings the STARG824NG control
board to factory settings.
m
This reset doesn’t affect memorized radio
transmitters (see par. 5 for radio trasmitters management).
1.
PRESS THE
START
BUTTON FOR 8 SECONDS OR UNTIL
ALL LEDS ARE FLASHING: all LED flash
2.
RELEASE
START
BUTTON
3.
PRESS
START
BUTTON FOR 3 SECONDS: all LED light up
in series
4.
RESET IS NOW COMPLETED: the
ERROR
led flashes 3
times continuosly
5.
A NEW PROGRAMMING OF THE GATE TRAVEL IS
REQUIRED