Chapter 3: Configuration and commissioning
54
KFP-CX3E Series Installation Manual
Earth fault check
Use this menu to configure the earth fault check, on or off. This determines
whether the earth fault is supervised or not. The default setting is On.
Note:
If disabled, it does not comply with EN 54-2 and EN 54-4.
To configure the earth fault check:
1. Set the display as shown below, and then press Enter.
The earth fault LED flashes fast to indicate that the battery fault check menu
is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your change
The available settings for this feature are shown below.
Display
Description
The earth fault check is enabled.
The earth fault check is disabled.
Fault latch
Use this menu to configure the fault latch, on or off. This determines whether the
power supply fault is latched or not. The default setting is On.
To configure the fault latch:
1. Set the display as shown below, and then press Enter.
The general fault LED flashes fast to indicate that the fault latch menu is
active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your change
Summary of Contents for KFP-CX3E Series
Page 1: ...KFP CX3E Series Installation Manual P N 501 419403 1 10 REV 01 ISS 12MAR14 ...
Page 6: ...iv KFP CX3E Series Installation Manual ...
Page 28: ...Chapter 2 Installation 22 KFP CX3E Series Installation Manual ...
Page 80: ...Chapter 3 Configuration and commissioning 74 KFP CX3E Series Installation Manual ...
Page 84: ...Chapter 4 Maintenance 78 KFP CX3E Series Installation Manual ...
Page 104: ...Appendix A Configuration presets 98 KFP CX3E Series Installation Manual ...
Page 108: ...Appendix B Regulatory information 102 KFP CX3E Series Installation Manual ...
Page 111: ......
Page 112: ......