Chapter 3: Configuration and commissioning
KFP-CX3E Series Installation Manual
33
To change the operation mode configuration preset:
1. Set the display as shown below, and then press Enter.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
Supervision mode
Use this menu to configure the supervision mode.
To configure the supervision mode:
1. Set the display as shown below, and then press Enter.
2. Select a value using the value selection buttons (2 and 4). The Zone LEDs
flashes fast to indicate that the supervision mode is active.
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
EN 54-13 supervision On for zone and class A
expansion board outputs.
Standard zone supervision with class B fire outputs
(default).
Note:
This menu is not visible if the panel operational mode is BS 7273 (either
stage 1 or stage 2) or includes CleanMe configuration. These options only allow
standard EN 54-2 zone supervision with class B outputs.
Panel mode
Use this read-only menu to view the operating mode of the control panel.
To view the panel mode:
1. Set the display as shown below, and then press Enter.
Summary of Contents for KFP-CX3E Series
Page 1: ...KFP CX3E Series Installation Manual P N 501 419403 1 10 REV 01 ISS 12MAR14 ...
Page 6: ...iv KFP CX3E Series Installation Manual ...
Page 28: ...Chapter 2 Installation 22 KFP CX3E Series Installation Manual ...
Page 80: ...Chapter 3 Configuration and commissioning 74 KFP CX3E Series Installation Manual ...
Page 84: ...Chapter 4 Maintenance 78 KFP CX3E Series Installation Manual ...
Page 104: ...Appendix A Configuration presets 98 KFP CX3E Series Installation Manual ...
Page 108: ...Appendix B Regulatory information 102 KFP CX3E Series Installation Manual ...
Page 111: ......
Page 112: ......