Chapter 3: Configuration and commissioning
KFP-CX3E Series Installation Manual
49
The available settings for this feature are shown below.
Display
Description
Flooding time is enabled.
Flooding time is disabled.
Flooding time
Use this menu to set the flooding time for the actuator (5 to 300 seconds in steps
of 5 seconds). When the actuator is activated, the flooding time delay starts to
run. When the flooding time expires, the actuator output is deactivated.
The default value is 0 min, 0 sec.
The maximum value is 5 min.
If the flooding time is set to 0 min, 0sec., the ‘flooding time enable’ will be set to
OFF.
To configure the flooding time:
1. Set the display as shown below, and then press Enter.
The red Released LED flashes fast to indicate that the configuration menu is
active and nn (minutes) and SS (seconds) appears.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Setting the number of minutes (range is from 0 to 5).
Setting the number of seconds (range is from 0 to 55).
Summary of Contents for KFP-CX3E Series
Page 1: ...KFP CX3E Series Installation Manual P N 501 419403 1 10 REV 01 ISS 12MAR14 ...
Page 6: ...iv KFP CX3E Series Installation Manual ...
Page 28: ...Chapter 2 Installation 22 KFP CX3E Series Installation Manual ...
Page 80: ...Chapter 3 Configuration and commissioning 74 KFP CX3E Series Installation Manual ...
Page 84: ...Chapter 4 Maintenance 78 KFP CX3E Series Installation Manual ...
Page 104: ...Appendix A Configuration presets 98 KFP CX3E Series Installation Manual ...
Page 108: ...Appendix B Regulatory information 102 KFP CX3E Series Installation Manual ...
Page 111: ......
Page 112: ......