Chapter 3: Configuration and commissioning
KFP-CX3E Series Installation Manual
31
Basic configuration
The default password for basic configuration is 3333. After entering the
password, the first displayed menu will be Basic default configuration (indicating
the basic installer user level). For more information see “User level passwords
and indications” on page 27.
The basic configuration menu
Configuration options for this menu are shown in the table below. More
information for each option is included in the related topic.
Table 13: The basic configuration menu
Display
Menu
Values
Basic default configuration
01, 02, 05, 06, 11,12, 13, 14, 61, 63
EN 54-13 supervision
Of= EN54-13 supervision Off and
class B outputs
A= EN54-13 supervision On for
zone and class A expansion board
outputs
Default: Off
Panel mode
Basic standard
Basic evacuation
BS 7273 mode stage 1
BS 7273 mode stage 2
Repeater with fire routing (EN 54-2)
Repeater with fire routing (BS 7273)
Custom
Actuator delay
00 to 60 seconds
Default: 10 seconds
Reset disabled delay
00 to 30 minutes
Default: 2 minutes
Fire sounders delay
00 to 10 minutes
Default: 0 minutes
Fire routing delay
00 to 10 minutes
Default: 0 minutes
Add an expansion board [1]
00 to 04 modules
Default: 0
Firenet identifier [2]
0 to 32
0: Stand-alone (no networking)
Default: 0
Summary of Contents for KFP-CX3E Series
Page 1: ...KFP CX3E Series Installation Manual P N 501 419403 1 10 REV 01 ISS 12MAR14 ...
Page 6: ...iv KFP CX3E Series Installation Manual ...
Page 28: ...Chapter 2 Installation 22 KFP CX3E Series Installation Manual ...
Page 80: ...Chapter 3 Configuration and commissioning 74 KFP CX3E Series Installation Manual ...
Page 84: ...Chapter 4 Maintenance 78 KFP CX3E Series Installation Manual ...
Page 104: ...Appendix A Configuration presets 98 KFP CX3E Series Installation Manual ...
Page 108: ...Appendix B Regulatory information 102 KFP CX3E Series Installation Manual ...
Page 111: ......
Page 112: ......