Chapter 2: Installation
KFP-CX3E Series Installation Manual
11
Connecting extinguishing system manual call points
The manual call point inputs require an activation impedance between 100 and
620
Ω, 2 W. These are normally connected in series with a normally open (NO)
contact. An end-of-
line resistance of 15 kΩ is required.
When the abort extinguishing or hold extinguishing manual call points are
activated, the control panel activates the related relay outputs on the main board.
Note:
MCP Hold faults and MCP Abort faults prevent the panel from entering the
extinguishing activation state (because of life safety issues) and from activating
the actuator (to ensure property protection).
The extinguishing system supports three types of manual call point (MCP):
• MCP Start
• MCP Hold
• MCP Abort
Descriptions of each MCP type follow.
MCP Start.
Starts the extinguishing process. When the panel is in the standby,
extinguishing preactivation, or fire alarm state, activation of this device puts the
panel in the extinguishing activation state.
The control panel can be configured to bypass any actuator delay and to activate
the actuator immediately on entering the extinguishing activation state. To
configure this, set the “Actuator delay for Start MCP” to OFF.
MCP Hold.
Holds the extinguishing process. When the panel is in the
extinguishing activation state, the actuator output is not activated while the MCP
Hold device is activated (continuously). The MCP Hold input can be configured
for two different operating modes, Mode A and Mode B.
Table 7: MCP Hold operating modes
Mode
Description
Mode A
When the MCP Hold is activated, the actuator delay countdown continues,
but the panel is prevented from entering the extinguishing activation state.
When the MCP Hold is deactivated, the delay countdown determines when
the panel enters the extinguishing activation state.
In this mode, activation of the MCP Hold turns on the MCP Hold LED, which
stays on until the panel is manually reset. The yellow Preactivation LED
flashes to indicate that the panel is being prevented from entering the
extinguishing activation state. The Preactivation LED flashes to show when
the MCP Hold is on; it turns off when the MCP Hold is off.
Mode B
When the MCP Hold is activated, the actuator delay countdown stops, putting
the extinguishing release process on hold. The sounders emit a unique
sound pattern (1 second on, 4 seconds off) while the extinguishing release
process is on hold. When the MCP Hold is deactivated, the delay countdown
restarts and the sounder pattern changes to the tone configured for
extinguishing activation. The MCP Hold LED turns off when the MCP Hold
device is deactivated.
Summary of Contents for KFP-CX3E Series
Page 1: ...KFP CX3E Series Installation Manual P N 501 419403 1 10 REV 01 ISS 12MAR14 ...
Page 6: ...iv KFP CX3E Series Installation Manual ...
Page 28: ...Chapter 2 Installation 22 KFP CX3E Series Installation Manual ...
Page 80: ...Chapter 3 Configuration and commissioning 74 KFP CX3E Series Installation Manual ...
Page 84: ...Chapter 4 Maintenance 78 KFP CX3E Series Installation Manual ...
Page 104: ...Appendix A Configuration presets 98 KFP CX3E Series Installation Manual ...
Page 108: ...Appendix B Regulatory information 102 KFP CX3E Series Installation Manual ...
Page 111: ......
Page 112: ......