Chapter 3: Configuration and commissioning
KFP-CX3E Series Installation Manual
43
Pressure switch type
Use this menu to configure the low pressure switch for detection of the container
pressure. Correct pressure can be either normally closed (NC) or normally open
(NO). The default setting is normally closed (NC).
To configure the pressure switch type:
1. Set the display as shown below, and then press Enter.
The Low Pressure LED flashes fast to indicate that the configuration menu is
active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Operates as normally closed (NC).
Operates as normally open (NO).
Hold mode
Use this menu to set the operating mode for this device (mode A or B). The
default setting is mode A.
For a description of the emergency MCP Hold function and device, see
“Connecting extinguishing system manual call points” on page 11.
To configure the emergency hold device mode:
1. Set the display as shown below, and then press Enter.
The MCP Hold LED flashes fast to indicate that the configuration menu is
active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
Summary of Contents for KFP-CX3E Series
Page 1: ...KFP CX3E Series Installation Manual P N 501 419403 1 10 REV 01 ISS 12MAR14 ...
Page 6: ...iv KFP CX3E Series Installation Manual ...
Page 28: ...Chapter 2 Installation 22 KFP CX3E Series Installation Manual ...
Page 80: ...Chapter 3 Configuration and commissioning 74 KFP CX3E Series Installation Manual ...
Page 84: ...Chapter 4 Maintenance 78 KFP CX3E Series Installation Manual ...
Page 104: ...Appendix A Configuration presets 98 KFP CX3E Series Installation Manual ...
Page 108: ...Appendix B Regulatory information 102 KFP CX3E Series Installation Manual ...
Page 111: ......
Page 112: ......