Chapter 3: Configuration and commissioning
38
KFP-CX3E Series Installation Manual
Display
Menu
Values
Panel mode
Basic standard
Basic evacuation
BS 7273 mode stage 1
BS 7273 mode stage 2
Repeater with fire routing (EN 54-2)
Repeater with fire routing (BS 7273)
Custom
Actuator delay
00 to 60 seconds
Default: 10 seconds
Reset disabled delay
00 to 30 minutes
Default: 2 minutes
Safety door monitoring
ON/OFF
Default: Off
Safety door fault delay
10 to 90 seconds
Default: 30 seconds
Pressure switch type
Normally closed
Normally open
Default: Normally closed
Activation tone
Pulsed
Continuous
Default: Pulsed
Released tone
Pulsed
Continuous
Default: Continuous
Extinguishing zones
Z1 extinguishing, Z2 and Z3 fire
Z1 and Z2 extinguishing. Z3 fire
Z1, Z2, and Z3 extinguishing
No extinguishing zones, Z1, Z2, Z3 fire
Default: Z1, Z2 – extinguishing, Z3 - fire
Manual-only mode local
ON/OFF
Default: On
Hold mode
Mode A
Mode B
Default: Mode A
Manual key mode
ON/OFF
Default: Off
Enable flooding time
ON/OFF
Default: Off
Flooding time
Minutes: 0 to 5
Seconds:0 to 55
Default: 0 minutes and 0 seconds
Actuator delay for start MCP
ON/OFF
Default: On
Summary of Contents for KFP-CX3E Series
Page 1: ...KFP CX3E Series Installation Manual P N 501 419403 1 10 REV 01 ISS 12MAR14 ...
Page 6: ...iv KFP CX3E Series Installation Manual ...
Page 28: ...Chapter 2 Installation 22 KFP CX3E Series Installation Manual ...
Page 80: ...Chapter 3 Configuration and commissioning 74 KFP CX3E Series Installation Manual ...
Page 84: ...Chapter 4 Maintenance 78 KFP CX3E Series Installation Manual ...
Page 104: ...Appendix A Configuration presets 98 KFP CX3E Series Installation Manual ...
Page 108: ...Appendix B Regulatory information 102 KFP CX3E Series Installation Manual ...
Page 111: ......
Page 112: ......