Chapter 3: Configuration and commissioning
40
KFP-CX3E Series Installation Manual
Display
Menu
Values
Firenet initial zone number
0001 to 9999
Default: 0001
The number has four digits. Identified
by position, these are: 1234.
Press Up to enter the first two digits of
the number (positions 1 and 2).
Press Down to enter the last two digits
of the number (positions 3 and 4).
Firenet global controls
ON/OFF
Default: On
Firenet loop class
A/ B
Default: B
Process remote zones
ON/OFF
Default: On
Firenet map
01 to 32
ON/OFF
On for nodes 1 and 2, Off for the rest
Firenet repeater map
01 to 32
ON/OFF
On for nodes 1 and 2, Off for the rest
Firenet analogue repeater remote node
ON/OFF
Default: Off
Firenet remote output control
ON/OFF
Default: Off
Extinguishing Firenet global controls
ON/OFF
Default: Off
Software version
Read-only
Configuration version
Read-only
Configuration time stamp
Read-only
Configuration date stamp
Read-only
Zone configuration
Passive EOL
Active EOL
Passive EOL with CleanMe
Active EOL with CleanMe
Intrinsically safe
Zenner EOL
Unlatched (only for BS 7273 mode and
fire zones)
Summary of Contents for KFP-CX3E Series
Page 1: ...KFP CX3E Series Installation Manual P N 501 419403 1 10 REV 01 ISS 12MAR14 ...
Page 6: ...iv KFP CX3E Series Installation Manual ...
Page 28: ...Chapter 2 Installation 22 KFP CX3E Series Installation Manual ...
Page 80: ...Chapter 3 Configuration and commissioning 74 KFP CX3E Series Installation Manual ...
Page 84: ...Chapter 4 Maintenance 78 KFP CX3E Series Installation Manual ...
Page 104: ...Appendix A Configuration presets 98 KFP CX3E Series Installation Manual ...
Page 108: ...Appendix B Regulatory information 102 KFP CX3E Series Installation Manual ...
Page 111: ......
Page 112: ......