Chapter 3: Configuration and commissioning
56
KFP-CX3E Series Installation Manual
Display
Description
Zenner end-of-line
Unlatched (only for BS 7273 mode and fire detection
zones)
Zone delay
Use this menu to configure zone delays, on or off, for each zone in your fire
alarm system. The default setting is On.
To configure the zone delay:
1. Set the display as shown below, and then press Enter.
2. Select the zone (for example, zone 1), and then press Enter.
The Zone alarm LED flashes fast to indicate that the corresponding zone
configuration menu is active.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
The available settings for this feature are shown below.
Display
Description
Configured delays are allowed in the corresponding
zone.
Configured delays are not allowed in the corresponding
zone
Zone type
Use this menu to configure the zone type for each zone in your system.
To configure the zone type:
1. Set the display as shown below, and then press Enter.
Summary of Contents for KFP-CX3E Series
Page 1: ...KFP CX3E Series Installation Manual P N 501 419403 1 10 REV 01 ISS 12MAR14 ...
Page 6: ...iv KFP CX3E Series Installation Manual ...
Page 28: ...Chapter 2 Installation 22 KFP CX3E Series Installation Manual ...
Page 80: ...Chapter 3 Configuration and commissioning 74 KFP CX3E Series Installation Manual ...
Page 84: ...Chapter 4 Maintenance 78 KFP CX3E Series Installation Manual ...
Page 104: ...Appendix A Configuration presets 98 KFP CX3E Series Installation Manual ...
Page 108: ...Appendix B Regulatory information 102 KFP CX3E Series Installation Manual ...
Page 111: ......
Page 112: ......