BOP HIPWR 080709
1-3
OUTPUT CHARACTERISTICS (Continued)
Sustain Output update rate
400 updates/sec
voltage or current
Readback
measurement rate
5 ms
measurement array
64 samples
voltage and current
step change timing
40
µ
sec (default)
Allows rejection of line-related ripple/noise by
changing response time for output step
change (see PAR. B.9).
Voltage stabilization in
voltage mode
source effect
0.05% of rating
min-max input voltage
load effect
0.1% of rating
0-100% load current
time effect (drift)
0.02 of rating
0.5 through 8 hours
temperature effect
0.02%/deg C of rating
0 to 50 deg C
ripple and noise
2% E0max p-p
Includes switching noise
Current stabilization in
current mode
source effect
0.05% of rating
min-max input voltage
load effect
0.2% of rating
0-100% load voltage
time effect (drift)
0.02% of rating
0.5 through 8 hours
temperature effect
0.02%/deg C of rating
0 to 50 deg C
ripple and noise
2% I0max p-p
Includes switching noise
Error sensing
0.25V per wire
Above rated output
Transient recovery in
voltage mode
maximum excursion
5% of nominal output
nominal voltage, 50% load step
Recovery time
200
µ
sec
Return within 0.1% of set voltage
Isolation
voltage
300V
Output to chassis ground
Series operation
Master/slave
Maximum of identical 3 units,
up to 300V max.
Parallel operation
Master/slave
Maximum of 5 identical units
Series-parallel Opera-
tion
2 series x 2 parallel
3 series x 2 parallel
Master/slave for both series and parallel
branches of identical units
Output Protection limit-
ing
voltage and current limited in four quadrants, adjustable between ±Internal minimum
EO
MIN
or IO
MIN
(box) (see Figure 1-3) and ±1.01 EO
NOM
or IO
NOM
.
Output Stage Protection
Output overvoltage/overcurrent
Heatsink overtemperature,
switchers overcurrent
Triggers latched shutdown protection of the
output module and PFC stage. Recover by
cycling power off, then on or by pressing
RESET
at the front panel.
Input Stage Protection (PFC)
Internal overvoltage, undervoltage,
overcurrent, heat sink
overtemperature, fan inoperative
Input circuit breaker overcurrent
Trips circuit breaker to shut off unit
Small signal
Bandwidth
voltage channel
2 KHz minimum
Into nominal resistive load 10% of rating
current channel
800 Hz minimum
Into short circuit, 10% of rating
Rise/Fall time
voltage channel
250/200
µ
Sec
Into nominal resistive load, measured from 10
to 90%, from 0 to ±100% of rating
current channel
0.7/1.2 mSec
Into short circuit, measured from 10 to 90%,
from 0 to ±100% of rating
TABLE 1-2. BOP GENERAL SPECIFICATIONS (Continued)
SPECIFICATION
RATING/DESCRIPTION
RATING/DESCRIPTION
Summary of Contents for BOP 1000W
Page 2: ......
Page 10: ......
Page 20: ......
Page 31: ......
Page 32: ......
Page 36: ......
Page 50: ...FIGURE 2 2 LOAD CONNECTIONS LOCAL SENSING...
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 64: ......
Page 68: ...FIGURE 3 3 POWER UP SCREEN SHOWING GRAPHIC METERS VOLTAGE 0000 0...
Page 125: ......
Page 128: ......