1-4
BOP HIPWR 080709
PROGRAMMING/DISPLAY CHARACTERISTICS
Analog I/O Port
(See Table 2-10)
Main
channel
(voltage or current)
–10V to +10V
Full range output, 20K Ohm input impedance
(see PAR. 3.4)
Protection Limit
channels:
(±Voltage, ±Current)
+1V to +10V
10% to 100% of Nominal Range. Input voltage
clamped to 12V through 1K ohms. Maximum
of 0.15mA input current at1V input voltage.
Mode Control
Voltage: open circuit or TTL logic 1
Current: short circuit or TTL logic 0
Available only when digitally activated through
Power-up setting..
Output Current
Analog Readback
0 to ±10 Volts corresponds to zero to
± Full Scale nominal output current
Output impedance of this signal is 2K Ohms.
External Protection Port
(see Table 2-4)
External Shutdown
Isolated input for shutdown of the
BOP (latched status)
Pulse width: 100 microseconds min.
Action delay: 100 microseconds max
Restore operation by cycling input power or
pressing
RESET
key.
External Shutdown
Flag
Isolated output indicating
shutdown status)
Action delay: 100 microseconds max
External On-Off
Flag
Isolated output indicating
output on (enabled, STANDBY off) or
off (disabled, STANDBY on) status)
Action delay: 200 milliseconds max
Trigger Port
(See Table 2-3)
External Trigger
Shutdown
Isolated input for setting the BOP
in STANDBY (output off)
(latched status)
Pulse width: 100 microseconds min.
Action delay: 200 milliseconds max
Restore operation by pressing
STANDBY
key.
or sending OUTP ON command via remote
interface.
External Trigger
Input
Isolated input for trigger events
Pulse width: 100 microseconds min.
Action delay: 500 microseconds max
Digital control
local
Panel-mounted keypad
Direct Entry
remote
IEEE 488-2 (GPIB)
SCPI
remote
RS 232
remote
RS 485 (BITBUS)
IEEE 1118
Display
front panel
4" backlit LCD displays all functions
remote
All parameters read back on GPIB or RS 232 buses
FUNCTION GENERATOR CHARACTERISTICS
(See PAR. 3.3.9)
Maximum number of waveforms
Local: 16
Remote: 1
Local: Saved for power-up
Remote: Lost when the unit is turned off, must
be saved on the host computer)
Maximum number of segments or basic wave-
forms per waveform
Local: 10
Remote: 126
Or maximum number of points (whichever
comes first)
• The time interval for each segment
depends on the type of waveform: period
for ramp and square waveforms, period or
fraction of period for sine and triangular
waveforms and time interval for DC levels
• Segments that cause the waveform to
exceed the maximum number of points are
not executed. For local operation they are
marked with a triple asterisk on the front
panel. For remote operation an error mes-
sage is generated.
TABLE 1-2. BOP GENERAL SPECIFICATIONS (Continued)
SPECIFICATION
RATING/DESCRIPTION
RATING/DESCRIPTION
Summary of Contents for BOP 1000W
Page 2: ......
Page 10: ......
Page 20: ......
Page 31: ......
Page 32: ......
Page 36: ......
Page 50: ...FIGURE 2 2 LOAD CONNECTIONS LOCAL SENSING...
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 64: ......
Page 68: ...FIGURE 3 3 POWER UP SCREEN SHOWING GRAPHIC METERS VOLTAGE 0000 0...
Page 125: ......
Page 128: ......