Configuration method
Configuration method
Configuration method
Configuration method
4-6
[3--] Volume Setting
[3-1] Linearization Selection
Parameter
Value
Description
0
Not Calculated
1
Vertical Cylinder
2
Spherical
3
Horizontal Cylinder
4
User Tank Table
Tank Configurations
[3-2] Linearization Point Number
Parameter
Default Value
Description
0-20
0
Input required no. of points for table
[3-3] Level point
(
[300] ~ [319]
)
Parameter
Default Value
Description
-3.000-23.000
0.000
Parameter range in metric [m] units
If measurement unit is [ft], display will be converted to show ‘feet’ units
[3-4] Volume point
(
[320] ~ [339]
)
Parameter
Default Value
Description
0-99999.99
0.000
Display will be converted to the volumetric unit setting under [3-9].
If you create a volumetric table incorporating settings [3-2] ~ [3-4], you can produce a line chart
such as that shown below which enables you to quickly calculate level and volumetric values.
3
2
1
4
19
20
[300] [301]
[302]
[303]
[318]
[319]
[320]
[321]
[322]
[323]
[338]
[339]
Volume point Number on [3-2]
Volume table on [3-4]
Volume
Level
Level table on [3-3]
Level and Volume correlation on the user tank table
1: Vertical Cylinder
2: Spherical
3: Horizontal Cylinder